Gas Engineering Guide

Air – Louvers and Grilles

In calculating free area as required, consideration shall be given to the blocking effects of louvers, grilles, or screens protecting such opening. Screen mesh used shall not be smaller than 1/4 inch. (NFPA 54, 9.3.7.2). If the free area through the design of louver or grille is known, it shall be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will have 25% free area, and metal louvers and grilles will have 75% free area. (NFPA 54, 9.3.7.1).

Hurricane Lowell update for Kauaʻi customers: The Hawai'i Gas Kauaʻi office is currently closed due to impacts from the storm. For service requests, please leave a voice message at (808) 245-3301 and we will return your call as soon as possible.  If you detect a gas leak, call 911 or the Hawai'i Gas emergency line at (808) 526-0066. For more safety resources visit hawaiigas.com.